Idroelettrica

FIREBOX VTP

Firebox VTP

Outdoor fire protection modules prefabricated to UNI11292 standards with UNI EN12845 Fire Protection Group WITH VERTICAL TURBINE PUMPS (VTP)

Download

Data sheet

Description

MAIN FEATURES

FIREBOX VTP is a complete and autonomous fire-fighting room for systems that use vertical pumps (VTP) The vertical pumps can be connected to both electric and diesel engines and guarantee high operating reliability and for this reason they are used in important works. The FIREBOXES, where units with VERTICAL TURBINE PUMPSare housed, are made with a removable roof to make any maintenance operation even easier.
  • Walls made with sandwich panels, fully openable
  • Total accessibility for people and for the handling of the components
  • Perfectly compliant with technical standards and legal provisions
  • Designed to be installed in seismic area
  • Absence of stairs and dangers for the safety of people
  • R60 load-bearing structure
  • Easy to disassemble and transport
  • UNI 1090 certificate and produced entirely in IDROELETTRICA SPA production plants
  • CE certification according to the Machinery Directive 2006/42/EC
  • Can be used with existing underground water storage
 

ADVANTAGES

FIREBOX VTP complies with all the points contained in the UNI EN 12845, UNI 11292, UNI 10779, CEI 64-8 standards, and the provisions of Ministerial Decree 81/2008 (Consolidated Law on Workplace Health and Safety).
  • Using the FIREBOX with vertical pumps immersed in axial flow (UNI EN 12845/10.6.1) one gets the enormous advantage of having an arrangement that is always suction lift, even with the underground accumulation tank.
  • For these reasons, FIREBOX VTP is the best alternative to the outdated integrated systems run completely from underground.
  • The universal joint mounted between the corner drive and the diesel engine guarantees a perfect transmission of motion. It achieves vibration-free operation and smooth distribution of the motor. The use of other types of couplings could lead to rapid failure of the pump/diesel motor system.
 

MANUFACTURING SPECIFICATIONS

FIREBOX VTP is designed and built following the indications of UNI 1090 Part 1 and Part 2 (Execution of steel and aluminium structures - requirements for conformity assessment of the structural components). Compliance with this standard is indispensable to be able to build and correctly certify the metal carpentry made in the workshop. Only by complying with UNI 1090 can the metal structures be CE certified. FIREBOX VTP constitutes the envelope of the fire-fighting system, the load-bearing structure is made of steel profiles.
Load-bearing structure in steel profiles, calculated so as to achieve a fire resistance of 60 minutes (R60) - UNI EN 12845:2020 10.3.1.
The walls of the FIREBOX VTP are made of sandwich panels that are perfectly insulated thanks to the 80mm of rock wool (EI60).
 
Le pareti del FIREBOX VTP sono costituite da pannelli sandwich perfettamente isolati grazie agli 80mm di lana di roccia (EI60).

 

APPLICATIONS

{​​​​​SHOPPING CENTERS

{HOSPITALS

{INFRASTRUCTURE

{INDUSTRIES

{HOTELS

{RESIDENTIAL

{CINEMA AND THEATERS

{SCHOOLS

 

 

 

  • Fire protection by bulb sprinkler with flow status UNI EN 12845 10.3.2 (with any exclusions provided by UNI 10779).
  • Ventilation grid with dimensions according to UNI 11292 5.4.1
  • Alarm management panel A and B 220 V power supply complete with large battery charger buffer and siren with flashing light.
  • Flow meter complete with valve
  • Electric convector with antifreeze function 230 volt single-phase power supply, complete with built-in adjustable thermostat CE marked.
  • Lighting of the room, normal and emergency with lamps of adequate power and in compliance with UNI 11292
  • Fire extinguisher of class 34A144BC and, where applicable, extinguisher of class 113BC.
  • The electrical wiring is made with cables type FG 16 OM16-0.6/1kV, having a burning behaviour in accordance with CEI EN 60332-3-24 and a conductor diameter of at least 2.5 mm² of Cu (UNI EN 12845 –10.8.2).

 

 